This transmitter conditions a temperature signal so it can travel to the controller without picking up noise. Because it outputs a current rather than a resistance, a broken wire reads as a specific fault value instead of an open circuit - which makes wiring faults look like sensor faults.
Confirm the RTD type, the measuring range and the output wiring (2, 3 or 4 wire) before ordering. Check the resistance at the sensor terminals first - if the element is correct, the transmitter is the fault. Where the transmitter is loop powered, measure the supply at the terminals as well; a collapsed loop voltage reads exactly like a failed transmitter.